UV treatment + taste and odor treatment for drinking water
The TrojanUVSwift®ECT has been validated through microbial testing. Through this testing, performance data has been generated for UV dose delivery to inactivate microorganisms Cryptosporidium, Giardia, and Adenovirus.
When taste and odor events occur, additional UV lamps or chambers are energized and hydrogen peroxide is dosed into the water upstream of the UV system. This initiates a powerful oxidation reaction that breaks down MIB and Geosmin.
Sophisticated, patented control system optimizes the UV advanced oxidation process by controlling the dosing of hydrogen peroxide, lamp power and on/off status in real time. This minimizes operational costs while maintaining optimized UV energy distribution and hydrogen peroxide dosing.
For times when seasonal taste & odor treatment is not necessary, the system’s high intensity, medium-pressure UV lamps operate at lower energy levels that have been validated through microbial testing. Through this testing, performance data has been generated for UV dose delivery to inactivate microorganisms Cryptosporidium and Giardia.
Hydraulically efficient, flow-through design – developed through advanced Computational Fluid Dynamics modeling – minimizes head loss and pumping requirements. Full serviceability from one side of the chamber allows installation in restrictive pipe galleries and against walls.
The optional dual-action ActiClean® sleeve cleaning system uses a combination of mechanical wiping and an NSF 60-certified gel to provide unparalleled sleeve cleaning. Quartz sleeves and intensity sensors are cleaned automatically, without disrupting treatment.
Model | L24 |
Number of Lamps | 8 |
Dimensions/Miscellaneous | |
Approximate Dimensions | |
Width (in/m) | 54/1.4 |
Length (Flange to Flange) (in/m) | 35/0.9 |
Overall Height (in/m) | 38/1.0 |
Required for Service beyond End Cap (in/m) | 24/ 0.6 |
Vertical Distance Required for Service (in/m) | 88/2.2 |
Maximum Operating Pressure (PSI/kPa) | 150/1,034 |
Dry Chamber | Wet Chamber Weight (lb/kg) | 1,500/680 | 2,240/1,016 |
Electrical/Control Power Panel | |
Electrical Supply | 480 V, 3 Ph + GND, 60Hz; (400 V, 380 V, or 415 V), 3Ph + GND, 50 Hz |
Maximum Power Supply Range | 8 lamp - 83 kVA unbalanced |
Nominal kW Input per Lamp | 9.6
|
Panel Rating | Type 12 Indoor |
Enclosure Dimensions (HxWxD) | 86.75" x 94" x 23.5" | 2.2 m x 2.4 m x 0.6 m (4 cabinets per chamber [16L30]) |
Have questions? Call us at 1 (888) 220-6118 or complete the form below.